Input interpretation
saturation properties of refrigerants
Input values
saturation temperature | 5 °C (degrees Celsius) refrigerant | R134a
Results
saturation pressure | 0.3497 MPa | 3.451 atm | 50.71 psi | 2623 torr heat of vaporization | 194.7 kJ/kg | 83.72 BTU_IT/lb
Units
Chemical names and formula
name | 1, 1, 1, 2tetrafluoroethane IUPAC name | 1, 1, 1, 2-tetrafluoroethane formula | FCH_2CF_3
Saturation curve for R134a
Saturation curve for R134a
Additional properties at saturation
| liquid | vapor density | 1278 kg/m^3 | 17.13 kg/m^3 specific volume | 7.824×10^-4 m^3/kg | 0.05837 m^3/kg specific enthalpy | 206.8 kJ/kg | 401.5 kJ/kg specific entropy | 1.024 kJ/(kg K) | 1.724 kJ/(kg K)
Units
Temperature and pressure ranges for saturation properties
| triple point | critical point temperature | -103.3 °C | 101.1 °C | -153.9 °F | 213.9 °F pressure | 3.896×10^-4 MPa | 4.059 MPa | 0.003845 atm | 40.06 atm
Units